Product and Application Description
The RL 512/23 Switching actuator (relay) with mounting frame
is a KNX device with one switching output. The device is installed
in an AP 118 Control Module Box or an AP 641 Room
Control Box. The bus is connected via a bus terminal block. The
actuator electronics are supplied via the bus voltage.
The RL 512/23 can switch resistive loads (e.g. electrical heaters,
incandescent lamps, high voltage halogen lamps), inductive
loads (e.g. motor, low voltage halogen lamps with intermediate
conventional transformers), or capacitive loads (e.g. low voltage
halogen lamps with intermediate electronic transformers).
The actuator output may be configured independently to provide
switching, manual override, forced control, logical gate,
and status reporting. Furthermore, if required, time-limited
switching instead of permanent switching on can be enabled for
each channel via an optional "Night mode" object (e.g. for lighting
while cleaning), if need be with a warning before switching
off by multiple switching the output on and off (flashing).
Amongst others, the application program includes optional a
switching cycle and operating hours count with threshold monitoring
for each output and an integrated 8-bit scene control, in
which the output can be incorporated into up to 8 scenes.
Each output of the actuator may be set to one of the following
operating modes:
-
Normal operation
-
Timer operation