Description
The Modbus master RTU RS485 ekinex® EK-BH1-TP485
gateway is a KNX modular unit for panel mounting.
It allows you to exchange information with one or more
slave devices over a RS485 differential serial network
through Modbus RTU (Remote Terminal Unit) protocol.
The ekinex gateway acts as Modbus Master. The
information exchanged over the Modbus network are
updated over the KNX network by means of a twisted
pair (TP) communication cable.
The device manages a two-way data stream: the
Modbus registers can be cyclically read and their value
sent as a communication object over the KNX TP
network through a multicast communication to
configured group addresses. The data update over the
KNX network can be done cyclically and/or on event of
change of the data acquired by the Modbus network.
Likewise, the ekinex gateway can make requests to
cyclically readings KNX communication objects or
acquire their values during data exchange over the bus.
Cyclically or on event of change of the communication
objects, data are written on the Modbus registers of one
or more configured devices.
The ekinex gateway supports the entire Modbus RTU
master protocol with the possibility of reading and writing single and multiple 1-bit registers (Coil and
Status) as well as 16-bit registers (Holding and Input). It
is also possible to read and write multiple registers
containing 32-bit floating point values (IEEE 754 format).
As for KNX communication, 1-bit, 1-byte, 2-byte and 4-
byte communication objects can be acquired: internal
conversion functions allow you to convert the
information from and to 16-bit floating point values
(DPT 9.xxx) starting from integer Modbus registers.
Configuration is performed through a PC application
software which communicates through the integrated
Ethernet port. The application software
CGEKBH1TP485 is available for download at
www.ekinex.com.